NLD Series DIN Rail Industrial Power Supply, 120W 12VDC NLD-120-24
Product Description
|
Technical Specification |
NLD-120-24 |
Output Data |
DC Rated Voltage |
24V |
Output Voltage Range |
24V-28V |
Rate Output Current |
5A |
Load Regulation |
±1.0% |
Ripple & Noise |
120mV@25ºC |
Temperature |
±0.03%/ºC |
Overshoot Voltage |
≤5% |
Overshoot Voltage Range |
24V±5% |
Output Rise Time |
<100ms |
Power-on Delay |
≤3.0S@115Vac; ≤1.5S@230Vac |
Hold-up Time |
≥16ms@230Vac; ≥10ms@115Vac |
Capacitive Load |
500uF/A |
Input Data |
AC Voltage Range |
90-264Vac |
DC Voltage Range |
127-370Vdc |
Rate Voltage |
115Vac;230Vac |
Frequency Range |
47-63Hz |
PFC |
/ |
Inrush Current |
20A@115Vac; 35A@230Vac, 25ºC, cold start |
Standy Power Loss |
<1W@24Vdc |
Efficiency |
≥89.5%@230Vac full load |
Production |
Maximum Over Voltage |
30-35Vdc |
Over Current |
105%-130% |
Input Under Voltage Protection |
Hiccup operating mode |
Operating Environment |
Operating Temperature |
-20ºC~70ºC(>50ºC start to derating) |
Storage Temperature |
-40ºC~ 85ºC |
Humidity |
5%~95%(Non - condensing) |
Vibration Standard |
Acc.to IEC60068-2-6, 10 - 500Hz, 2G 10 min /1 cycle, 60 minutes per axis direction (X, Y, Z) |
Safety&EMC |
PE/CE |
EN55032/GB9254 Class B |
Harmonic Current |
IEC61000-3-2/GB17625.1 Class A |
Others |
Size |
40*125*107.8 mm |
Weight |
<0.55kg |
MTBF |
500,000 hours |

Certifications
Company Profile

Packaging & Shipping